Product Overview

The OZH4800E control panel is an analog addressable fire alarm panel using the latest 32
bit microprocessor technology and containing 2, 4, 6 or 8 SLC loops with each loop
supporting 192 devices of any combination (sensors or modules). Communication between
devices is transferred through standard cable (shielded or twisted pair is not required). Each
panel includes a 5.0 amp power supply, 600 characters LCD display, 29 large easy-to-use
tactile touchpad for system operation, programming and maintenance, 12 state indicators
and a RS232/RS485 communication port. System operations include silencing alarms and
troubles, resetting system and manual starting/stopping field equipment. The system’s
non-volatile event history buffer stores 9999 events for viewing. The system supports a
variety of Orena devices: smoke and heat sensors, manual call points, contact input
(monitor) modules, relay output modules, dual input/output modules, and short circuit
isolator modules. In addition, interfaces to conventional detection systems can be
established by using a conventional zone-monitoring module. The basic system can be
expanded by adding OZF-LCD remote annunciator, OZH48ZL signalling line circuit expander,
and optional mini-printer (for printing system reports). The intelligent panel and detectors
know the difference between a fire and a dirty sensor. It lets you tailor sensor sensitivity and
gives you immediate, pinpoint accuracy for any condition. The powerful OZH4800E system
provides you with revolutionary value and performance in addressable sensing technology,
reduces nuisance alarms and makes service calls a rarity.

Characteristics

  • Using advanced industry-standard protocol for fast and stable communication
  • Up to 1536 addressable points, 192 sensors & modules per loop
  • Uses standard wire, no shielded or twisted pair required on SLC loops
  • Supports Class B (style 4) and Class A (style 6 or 7) SLC loops
  • Automatic drift compensation & daily calibration
  • Programmable sensitivity levels per device
  • Large 15-line x 40-character LCD display (600 char.)
  • Built-in help information screens
  • Powerful & versatile Cause & Effect programming (fire protection-related device control)
  • RS-232 /485 communication port
  • Optional mini-printer

Specifications

Primary Power Supply: 120V or 220VAC 50/60Hz
Standby Batteries: DC24V 4AH sealed rechargeable batteries
Power Supply Output: 24VDC @ 5.0 Amps (4 Amps available for system power)
Display: 15 lines x 40 characters LCD (600 characters total)
SLC loops: 2, 4, 6 or 8 (class A, “style 6 or 7” or class B, “style 4”)
Devices per loop: 192 sensors & modules
Addresses per panel: 1536 max.
Communication Port: RS232/RS485
Operation Temperature: –10°C~+50°C Related Humidity: ≤95% (40±2°C)
Dimensions (D * W * H): 110×335×435mm Weight: 16Kg

SLC DEVICES & SYSTEM ACCESSORIES

OM622Addressable Dual Input Monitor Module

MODEL DESCRIPTION
OT602 Analogue Addressable Photoelectric Smoke Detector
OT603 Analogue Addressable Heat Detector
ODZ6004 4 inch Addressable Detector Base
OA610 Addressable Manual Call Point
OX620 Addressable Hydrant Button (waterproof)
OS631 Addressable Horn & Strobe
OM611 Addressable Supervised Relay Module
OM621 Addressable Dual Relay Output Module
OM612 Addressable Input Monitor Module
OM622 Addressable Dual Input Monitor Module
OM613 Addressable Conventional Zone Module
OM515 Short Circuit Isolator Module
OMDZ51 Module Base
OZH48ZL 4 Loops Expander Card (768 points)
OBM Hand Held Programmer (portable device addresser)
OZF-LCD LCD Remote Annunciator
OLK3908 LED Fire Indication Panel