Product Overview
The ODH2‐32 is a 24volt, 2, 4, 8, 16 or 32 Zone, Class B, Conventional Fire Alarm Control Panel with battery charger. It is designed exclusively to meet EN54‐2&4 standard and the latest market requirements. It has functions of operation indication, fault indication, alarm indication and cable checking for short circuit or broken circuit. The powerful and highly cost‐effective ODH2-32 can be used in low‐sized applications.
Characteristics
- Comply with EN54-2&4 standard
- Class B Initiating Device Circuits (IDC5) accept two-wire smoke detectors and any normally-open contact devices
- Key-switch/Password user control access
- 8-line x 16-character large LCD display screen with multi-language menu options
- Configurable detection zones (Latching/Non-latching/Enable/Disable)
- Remote panel inputs (Class Change/Evacuate/Silence Alarms/System Reset)
- 4 alarm circuits as standard on 4 zone panel upwards
- Configurable panel outputs (Fire Routing/Fault routing/Fire Protection)
- Remote panel outputs (Evacuate/Buzzer Active/Disablement Active)
- Programmable relay output (linkage control)
- Delay mode configuration options (0-180 seconds)
- Up to 10 fully functional repeaters connected via 2 core RS485 data cable
- Extensive configuration and programming options to cater for individual requirements
TECHNICAL SPECIFICATIONS
AC mains power supply | 187 – 242V AC/ 50Hz |
Battery | 2 /4 / 8 Zone 24V2.2Ah; 16 / 32 Zone 24V7Ah |
System power supply output | DC28V 3.0 amps |
Detection zone capacity | Up to 30 fire detectors and infinite manual call points |
Standby Current | 200mA |
Alarm Sounder circuit | 400mA Max current drive per circuit – Fully monitored |
Fire & Fault contact output | 1.0 amp DC24V or AC125V |
Using environment | Temperature: 0C’50C |
Related Humidity | 95% (40 士 2C) |
Dimensions | 370 x 320 x 130mm (length x width x depth) |
Weight | 6.2KGS (without batteries)/11KGS (with 7Ah batteries) |